Last modified:
About total outage alarms
Total outage alarms reflect a total outage of an inverter, a string combiner box, or the entire system. An alarm is triggered when the actual (measured) power drops below 1% of the nominal power.
Parameters
-
Monitoring period: To restrict alarms to daylight hours, tick the check box Sunrise to sunset and configure a delay if desired. If the incident occurs outside the defined time range, the alarm will be triggered once your defined time range begins.
-
Expected power: See Calculation methods for total outage and misproduction alarms.
-
Monitoring threshold: Monitoring begins once the expected power reaches the defined percentage of nominal power (= manufacturer's indication of the system's power output under normal conditions).
Example
For example, with a 100 kW system and a threshold set to 7.5%, the alarm is only triggered if the expected power exceeds 7.5 kW and the other trigger criteria are met.
-
Delay after first occurrence: If you configure a delay, an alarm will only be triggered in case of persistent incidents. This helps to avoid alarms for deviations that only occur for a short time.
Example
Based on the settings in the screenshot below:
-
No custom alarm profiles are used.
-
The monitoring period begins 30 minutes after sunrise and ends 30 minutes before sunset.
-
The machine learning simulation calculates the expected power.
-
When the monitoring threshold of 5% is exceeded, a critical alarm will be triggered if the outage persists beyond 30 minutes.
Custom alarm profiles
Note
When inverter comparison is used, either as the configured calculation method or as a fallback, inverter power below 1% of the inverter's nominal power is not used as the basis for comparison. Instead, the expected power is calculated based on the sun's position.
This also applies when an inverter is generating a small amount of power rather than exactly zero.