blue'Log XM/XC
Breadcrumbs

Janitza power analyzers

Last modified:

Device

Connections via Modbus TCP

Connection via Modbus RTU

blue’Log

Janitza

UMG 96

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/error.png

RS485 – A
RS485 – B

RS485 – A (17)
RS485 – B (16)

UMG 96 RM-E

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

RS485 – A (17)
RS485 – B (16)

UMG 96 RM-P

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/error.png

RS485 – A
RS485 – B

RS485 – A (17)
RS485 – B (16)

UMG 103 CBM

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/error.png

RS485 – A
RS485 – B

RS485 – A (2)
RS485 – B (3)

UMG 104

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/error.png

RS485 – A
RS485 – B

RS485 – A (23)
RS485 – B (22)

UMG 508

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

9-pole DSUB
socket

UMG 509

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

RS485 – A (2)
RS485 – B (3)

UMG 511

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

9-pole DSUB
socket

UMG 512

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

RS485 – A (2)
RS485 – B (3)

UMG 604

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

RS485 – A (23)
RS485 – B (22)

UMG 605

https://mc-help-center.atlassian.net/wiki/s/963856681/6452/95b70ecb409d2600298bab0a22e7cae056d6506a/_/images/icons/emoticons/check.png

RS485 – A
RS485 – B

RS485 – A (23)
RS485 – B (22)

For connections via Modbus TCP

  • Set the network parameters for the power quality analyzer. Data logger and power analyzer must be on the same subnet (net mask).

For connection via Modbus RTU

  • Set the bus address on the power analyzer (see power quality analyzer documentation).

  • If the device is the last one on the RS485 bus, terminate the bus with a 120 Ω terminating resistor.

  • To ensure sufficient query speed for the power control, it is recommended to operate the power analyzer as a single device on the bus.