VCOM Cloud

FCE/Full cycle equivalent KPI for battery units

Last modified:

The KPI for a battery unit’s FCE/Fully cycle equivalent is calculated by the portal at daily intervals.

Definition

The FCE KPI normalizes a battery unit’s partial charging and discharging within a time interval into an equivalent number of cycles, providing a consistent number of battery utilization over time.

Formula

Which formula is used to calculate the FCE KPI depends on whether the battery provides an FCE lifetime value or not.

A) Battery does provide FCE lifetime value

Some batteries already provide the data point B_FCE_COUNT at every measuring interval. It reflects the lifetime FCE since commissioning of the system. If it is available, you can find it in the data point category Batteries.

If B_FCE_COUNT is available, its measuring interval values are aggregated to the FCE daily value—the KPI.

B) Battery does not provide FCE lifetime value

If the portal can not use the B_FCE_COUNT, it must first calculate FCE values for every measuring interval in order to aggregate them to the FCE daily value. To do so, it uses measuring interval values of the charged and discharged energy:

FCE formula

Variable

Unit

Description

Further details

FCE

Full cycle equivalent

KPI only available as of daily values

Eexp

kWh

Exported/discharged DC energy

data point B_E_EXP or B_E_INT_EXP

Eimp

kWh

Imported/charged DC energy

data point B_E_IMP or B_E_INT_IMP

Enominal

kWh

Battery unit’s nominal capacity

configure separately

Further details and prerequisites

  • The KPI can only be used as daily or longer intervals. You can not display it in higher resolutions, like 15- or 1-minute intervals.

  • To perform the calculation, the data points B_E_EXP and B_E_IMP (lifetime values per measuring interval) are used. If these are not provided, B_E_INT_EXP and B_E_INT_IMP (measuring interval values) are used. See Import specification (external link).

  • You must configure the battery unit's nominal capacity in the portal. See Configure the battery units' operating parameters.

Usage

The FCE KPI can be used for the following functionalities:

Example

image-20260821-094629.png
User-defined chart displaying the FCE KPI

On 7th July, the unit Battery-Container 1 experienced a throughput equivalent to 2.91 complete charge-discharge cycles.