List of alarms/error codes

Last modified:


The following table describes the alarms (error codes, device events) generated by blue’Log. It also provides recommended actions and indicates whether the alarm can be read via SCADA. When an alarm is triggered, the information is sent via email or sent to VCOM.

Tip

image-20260401-134503.png Expand the table for a full view.


Error code

Description

Alarm type

Closes when?

Recommendation

Read via SCADA Interface?

POWER_CONTROl_ALARM_DB_FULL

The database for power control alarms is full

System

Automatically the next day (0:00)

Check the detected alarms. Fix the underlying issues or contact meteocontrol support.

ERROR 1: Registers 40500 & 40501

Bitcode: 0x0002

STATE_DB_FULL

State database is full / the device alarming was deactivated

System

Automatically the next day (0:00)

Check the detected states and contact the device manufacturer if necessary for further clarification.
You can also exclude undesired notifications via the filter feature under Plant > Alarm/state configuration.

ERROR 1: Registers 40500 & 40501

Bitcode: 0x0008

SYSTEM_ALARM_DB_FULL

SYSTEM_ALARM_DB_FULL

System

Automatically the next day (0:00)

Check the detected alarms and contact the device manufacturer if necessary for further clarification.
You can also exclude undesired notifications via the filter feature under Plant > Alarm/state configuration.

ERROR 1: Registers 40500 & 40501

Bitcode: 0x0010

ALARM_DB_FULL

Alarm database is full / device alarming was deactivated

System

If there is enough free space: the oldest entries are deleted the following day.

Check the detected alarms and contact the device manufacturer if necessary for further clarification.

ERROR 1: Registers 40500 & 40501

Bitcode: 0x0004

EXTERNAL_POWER_DISPLAY

The maximum pulse rate of 16 Hz was exceeded

System

Resolved

Choose a smaller number of impulses per kWh.

cross mark

MAX_POWER_EXCEEDED

Maximum allowed total power exceeded

System

Resolved

Contact the meteocontrol sales department to buy a larger license.

ERROR 1: Registers 40500 & 40501

Bitcode: 0x0001

PASSWORD_FORGET

Password forgotten triggered

System

Resolved

Check your email inbox and enter the code you received in the blue'Log. In addition, enter a new password.

cross mark

NOCOMM_RS485

Communication failure (RS485)

Device and device communication

Resolved

Check if the device is working, if there is a cable connection or if the communication interface of the device is configured/activated correctly.

cross mark

NOCOMM_TCP

Communication failure (TCP)

Device and device communication

Resolved

Check if the device is working, if there is a cable connection, or if the communication interface of the device is configured/activated correctly.

cross mark

NOTIMPL_FEAT_GET_VALUE

Get value not supported

Device and device communication

Resolved

Contact meteocontrol support.

cross mark

NOTIMPL_FEAT_PC

Power control not supported

Device and device communication

Resolved

Contact meteocontrol support.

cross mark

NOTIMPL_FEAT_SCAN

Device scan not supported

Device and device communication

Resolved

Contact meteocontrol support.

cross mark

NOTIMPL_FEAT_SET_VALUE

Set value not supported

Device and device communication

Resolved

Contact meteocontrol support.

cross mark

NOTIMPL_FEAT_START_STOP

Start/Stop not supported

Device and device communication

Resolved

Contact meteocontrol support.

cross mark

STATUS

Abnormal state

Device and device communication

Resolved

None

cross mark

CABLE_BREAKAGE

Setpoint value cannot be determined as cable breakage was detected

Power control

Resolved or PC restarts

Check configuration and interface for setpoint command via analog signal (0/4 ... 20 mA).

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0010

FEED_IN_METER_FAILURE

Actual value for measured value feedback is missing

Power control

Resolved or PC restarts

Check meter configuration and interface for recording of utility measurements.

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0040

GRID_DISCONNECT

Automatic grid disconnection tripped

Power control

Resolved or PC restarts

Check the power control settings if automatic grid disconnection occurs too frequently.

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0080

LFSMO_ACTIVATED

Limited frequency sensitive mode - overfrequency (LFSM-O) activated because the actual system frequency is above the configured frequency threshold

Power control

Immediately after P control goes back into normal operation. For this, the Resolved alarms/states toggle must be activated.

None

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0100

LFSMU_ACTIVATED

Limited frequency sensitive mode - overfrequency (LFSM-U) activated because the actual system frequency is under the configured frequency threshold.

Power control

Immediately after P control goes back into normal operation. For this, the Resolved alarms/states toggle must be activated.

None

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0200

P_SET_POINT_MISSING

Setpoint value for active power control is missing

Power control

Resolved or PC restarts

Check configuration and interface for active power setpoint commands.

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0004

Q_SET_POINT_MISSING

Setpoint value for reactive power control is missing

Power control

Resolved or PC restarts

Check configuration and interface for reactive power setpoint commands.

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0008

SYSTEM_FALLBACK

Fail-safe operation was activated, and a system fallback value is used as setpoint until a valid setpoint is received

Power control

Immediately, if Resolved alarms/states toggle is activated.

Check configuration and interface for the setpoint command or change mode for behavior in event of error.

cross mark

TRANSMITTER_FAULT

Setpoint value cannot be determined as transmitter fault (overcurrent) was detected.

Power control

Resolved or PC restarts

Check configuration and interface for setpoint command via analog signal (0/4 ... 20 mA).

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0020

ACTIVE_METER_FAILURE

Actual value for measured value feedback is missing

Power control

Resolved: the meter for active power is communicating correctly with the data logger.

Check meter configuration. Check the interface to ensure measurements are being logged.

ERROR 2: Registers 40502 & 40503

Bitcode: 0x0040

REACTIVE_METER_FAILURE

Actual value for measured value feedback is missing

Power control

Resolved: the meter for reactive power is communicating correctly with the data logger.

Check meter configuration. Check the interface to ensure measurements are being logged.

ERROR 2: Registers 40502 & 40503

Bitcode: 0x1000

VPN_INTERRUPTED

The OpenVPN connection was interrupted during operation. The device attempts to re-establish the connection on its own, if nothing else is specified by the OpenVPN server.

System

Immediatelay after VPN reconnects

If the connection is not restored automatically, check if the OpenVPN server is working or contact the server operator if necessary.

cross mark

CONTROLLER_FREEZE

Controller freeze (voltage event). The active and reactive power correction values sent to the inverters are frozen due to an over- or undervoltage event.

Power control

Comes back to normal state and when PC restarts

None

cross mark