Last modified:
Note: Beta feature
Telecontrol is currently available as a beta feature
You can configure an IEC server in two ways:
-
Option 1: Manually configure a server: If no grid operator template is available or when you need complete control over the server and data point configuration.
-
Option 2: Import a pre-filled grid operator template: When a predefined template is available. Templates include pre-filled IEC data point definitions and can significantly reduce setup effort.
Regardless of the method you choose, you must review the configuration and complete any project-specific settings before using the server.
Prerequisites
-
IEC clock synchronization is configured under Settings > Date/Time > Time synchronization > select IEC - Clock synchronization.
-
The required communication interface is configured (RS-485 for 101, Ethernet for 104).
-
Network and (optional) firewall settings allow communication with the grid operator.
Caution
The server is active by default. If you do not want to exchange data with the grid operator during setup, deactivate the
Warning
To prevent data loss, export the configuration as a backup after completing the server and data point configuration.
Option 1: Manually configure an IEC server
Steps
-
Go to Telecontrol > Configuration > Add new IEC server configuration.
-
A new IEC server configuration is created.
-
On the Interface tab, choose protocol 101 or 104 from the dropdown.
-
Different fields will appear depending on the selected protocol.
-
Configure the fields in the Interface, Protocol, and General configuration tabs. Find descriptions of the fields in the tables below.
-
Select Save.
You can now configure data points on the server.
Protocol 101 (RS-485)
Protocol 104 (Ethernet)
Note
The maximum telegram length is fixed to 255 bytes.
Option 2: Import a pre-filled grid operator template
The bluelog provides a selection of grid operator templates that contain pre-filled IEC data point configurations, such as addressing, transmission modes, and mapping definitions. The pre-filled data point definitions apply to the standard data points listed for the specific grid operator.
Templates do not define actual values for device data points (inverters, etc.) or default values for data points. You must define these after loading the template.
Import a template
Steps
-
Go to Telecontrol > Configuration.
-
Select Load configuration.
-
Select Import from template.
-
Select the relevant template from the dropdown.
-
Select Apply.
-
The configuration loads.
-
Remove any data points that are not defined in the data point list of your specific project (see examples below) and adapt configurations as necessary.
You can now define default values for data points.
Example: Remove unnecessary data points
Templates may contain data points that are not relevant for your system. For example, you should remove data points that:
-
Belong to energy sources that are not installed, such as PV, BESS, or wind.
-
Refer to grid connection points that do not exist in your project.
Export and reuse configurations
Once you have configured the Telecontrol setup, you can export it locally. You can use this as a backup, and you can reuse it as a template on other bluelogs.
Export an IEC server configuration
Prerequisites
-
You have completed the Telecontrol configuration on a bluelog Neo.
Steps
-
On the bluelog, go to Telecontrol > Configuration.
-
Select Export configuration.
-
A JSON file is downloaded.
-
Save the file locally for reuse.
You can now reuse the server configuration.
Import a saved IEC configuration
Prerequisites
-
You have exported a Telecontrol configuration.
Steps
-
Go to Telecontrol > Configuration.
-
Select Load configuration.
-
A window appears. Select Import from file > Select file.
-
Select Save and activate.
-
Select Apply.
The configuration loads. You can now adapt the configuration as required.