Telecontrol: Add new server configuration

Last modified:

Note: Beta feature

Telecontrol is currently available as a beta feature

You can configure an IEC server in two ways:

Regardless of the method you choose, you must review the configuration and complete any project-specific settings before using the server.

Prerequisites

  • IEC clock synchronization is configured under Settings > Date/Time > Time synchronization > select IEC - Clock synchronization.

  • The required communication interface is configured (RS-485 for 101, Ethernet for 104).

  • Network and (optional) firewall settings allow communication with the grid operator.

Caution

The server is active by default. If you do not want to exchange data with the grid operator during setup, deactivate the image-20260721-072320.png Server active toggle until the configuration is complete.

❗

Warning

To prevent data loss, export the configuration as a backup after completing the server and data point configuration.

Option 1: Manually configure an IEC server

Steps

  1. Go to Telecontrol > Configuration > Add new IEC server configuration.

  2. A new IEC server configuration is created.

  3. On the Interface tab, choose protocol 101 or 104 from the dropdown.

  4. Different fields will appear depending on the selected protocol.

  5. Configure the fields in the Interface, Protocol, and General configuration tabs. Find descriptions of the fields in the tables below.

  6. Select Save.

You can now configure data points on the server.

Protocol 101 (RS-485)

Expand to view table

Tab

Item

Comment/Description

Interface

Interface

Select which RS-485 interface is used on the bluelog:

  • BM: Base module

  • MX: MX module

Baud rate

Select the server’s baud rate.

Frame settings

Define the serial communication format.

Protocol

Link address

Define the address (integer) of the remote IEC station receiving the communication. The link address must match the address configured on the connected device. Device ID / RTU Address.

Link address length

Number of bytes used to encode the link address. Must match the configuration of the remote station.

Cause of transmission length (COT)

Number of bytes used for the COT.

Common address length (COA)

Number of bytes used for the COA.

Information object address length (IOA)

Number of bytes used for information object addresses (data points).

Balanced mode

By default, the master/primary server initiates communication. Activate the toggle image-20260721-072320.png Balanced mode to allow both servers to initiate communication.

Poll rate

How frequently the master asks for new data.

Acknowledgement timeout (ms)

Maximum time to wait for a response or acknowledgement. A communication error is detected when the remote station does not answer in time.

General configuration

Counter Reporting Mode

Define how values are accumulated and sent: when requested, periodically, in real time, or with reset after reading.

Counter snapshot interval

Duration during which surveillance stops (Counter Reporting modes A & B only)

Report initialization mode

Decide whether to send all values at bluelog startup

Modbus sending interval

How often a telegram is sent to devices using output value points pointing to devices via Modbus.

Ageing interval

Period after which signals are ignored and the bluelog marks an IEC command with a timestamp as invalid.

Protocol 104 (Ethernet)

Expand to view table

Tab

Item

Comment/Description

Interface

Port

TCP port number

Protocol

Send window size

Maximum number of IEC telegrams that may be sent without receiving an acknowledgement.

Acknowledge window threshold (W)

Number of received telegrams that triggers an acknowledgement.

T1 Timeout

Maximum time to wait for an acknowledgement after sending data.

T2 Timeout

Maximum time an acknowledgement may be delayed for received data.

T3 Timeout

Maximum idle time before a connection test (keep-alive) is sent.

General configuration

Counter snapshot interval

Duration during which surveillance stops (Counter Reporting modes A & B only)

Report initialization mode

Decide whether to send all values at bluelog startup

Modbus sending interval

How often a telegram is sent to devices using output value points pointing to devices via Modbus.

Ageing interval

Period after which signals are ignored and the bluelog marks an IEC command with a timestamp as invalid.

Counter snapshot interval

Duration during which surveillance stops (Counter Reporting modes A & B only)

Note

The maximum telegram length is fixed to 255 bytes.

Option 2: Import a pre-filled grid operator template

The bluelog provides a selection of grid operator templates that contain pre-filled IEC data point configurations, such as addressing, transmission modes, and mapping definitions. The pre-filled data point definitions apply to the standard data points listed for the specific grid operator.

Templates do not define actual values for device data points (inverters, etc.) or default values for data points. You must define these after loading the template.

Import a template

Steps

  1. Go to Telecontrol > Configuration.

  2. Select Load configuration.

  3. Select Import from template.

  4. Select the relevant template from the dropdown.

  5. Select Apply.

  6. The configuration loads.

  7. Remove any data points that are not defined in the data point list of your specific project (see examples below) and adapt configurations as necessary.

You can now define default values for data points.

Example: Remove unnecessary data points

Templates may contain data points that are not relevant for your system. For example, you should remove data points that:

  • Belong to energy sources that are not installed, such as PV, BESS, or wind.

  • Refer to grid connection points that do not exist in your project.

Export and reuse configurations

Once you have configured the Telecontrol setup, you can export it locally. You can use this as a backup, and you can reuse it as a template on other bluelogs.

Export an IEC server configuration

Prerequisites

  • You have completed the Telecontrol configuration on a bluelog Neo.

Steps

  1. On the bluelog, go to Telecontrol > Configuration.

  2. Select Export configuration.

  3. A JSON file is downloaded.

  4. Save the file locally for reuse.

You can now reuse the server configuration.

Import a saved IEC configuration

Prerequisites

  • You have exported a Telecontrol configuration.

Steps

  1. Go to Telecontrol > Configuration.

  2. Select Load configuration.

  3. A window appears. Select Import from file > Select file.

  4. Select Save and activate.

  5. Select Apply.

The configuration loads. You can now adapt the configuration as required.