Data cables must be separated from live power supply cables by means of a metal cable support system in accordance with DIN EN 50174-2: 2018-10.
Shielding
The cable shielding may only be grounded at one end of the connection.
Recommended wire and cable types
The table below lists recommended cable types for wiring the individual system components as well as restrictions.
|
Type |
Product designation |
Item number |
Max. permissible length |
|---|---|---|---|
|
Bus cabling (devices)
|
UNITRONIC Li2YCYv (TP) data cable 2x2x0.50 mm² 1) 2) |
200.116 |
1200 m 2) |
|
UNITRONIC Li2YCYv (TP) data cable 3x2x0.50 mm² 1) |
200.117 |
||
|
UNITRONIC Li2YCYv (TP) data cable 4x2x0.50 mm² 1) |
200.118 |
||
|
Analog signals (irradiance sensor, temperature sensor)
|
UNITRONIC Li2YCYv (TP) data cable 2x2x0.50 mm² 1) |
200.116 |
100 m |
|
UNITRONIC Li2YCYv (TP) data cable 3x2x0.50 mm² 1) |
200.117 |
||
|
UNITRONIC Li2YCYv (TP) data cable 4x2x0.50 mm² 1) |
200.118 |
||
|
Digital signals (status messages, remote control systems)
|
UNITRONIC Li2YCYv (TP) data cable 2x2x0.50 mm² 1) |
200.116 |
600 m 3) |
|
UNITRONIC Li2YCYv (TP) data cable 3x2x0.50 mm² 1) |
200.117 |
||
|
UNITRONIC Li2YCYv (TP) data cable 4x2x0.50 mm² 1) |
200.118 |
||
|
Temperature sensor (PT 1000) Meter with S0 (digital pulse) signal |
UNITRONIC Li2YCYv (TP) data cable 2x2x0.50 mm² 1) |
200.116 |
30 m |
|
Ethernet network
|
At least CAT 5/6 S/FTP |
n/a |
100 m 2) |
1) This cable is suitable for laying in the ground in a conduit. Repeaters must be used for longer cable lengths.
2) A hub is required if multiple separate cables of this length are used.
3) A power supply of 24 V DC is required.