blue'Log XM/XC
Breadcrumbs

meteocontrol i’catcher series

Last modified:


Valid for:

  • i’catcher 8-8

  • i’catcher 8-1B

  • i’catcher 16-1Bi’catcher 24-1B (Modbus RTU)


  • Set the bus address on the i'catcher (see i'catcher documentation).

  • If the device is the last one on the RS485 bus, set the terminating switch (Term.) to "On". Since the i'catcher 8-8 has no terminating switches, the bus must be terminated regularly with a 120 Ω resistor between wires A and B.

  • Various Modbus devices can only be queried together if the serial communication parameters are identical (baud rate, number of data bits, parity, stop bits).

icatcher series_string monitoring connection
i’catcher series: String monitoring connection


Description

1

Data logger terminal, RS485

2

First and subsequent i’catchers

3

Last i’catcher