User-defined static alarms

Last modified:

With user-defined static alarms, you can monitor single data points for your devices. For example, you can detect a deviation from a defined measured value, such as inverter frequency on individual devices. For this, threshold values are defined (maximum, minimum, or permissible range). This alarm is triggered if the monitored data point exceeds or falls below the threshold value. You define the device type, criteria, and delay for generating each specific user-defined static alarm.

Example

Based on the settings in the screenshot below:

  • An alarm with the severity “normal” will be triggered if the inverter frequency on Inverter 1.1 or Inverter 1.2 is outside the range of 49.98-50.02 Hz.

  • The alarm will only be triggered between sunrise and sunset, and if the incident persists beyond 30 minutes.

    User-defined static alarm settings

    User-defined static alarm settings