Zero feed-in and automatic grid disconnection (without HEMS)
About zero feed-in and automatic grid disconnection
Zero feed-in, or zero export refers to a situation where a renewable energy system does not export excess electricity to the grid. Instead, all the electricity generated by the system is consumed on-site or stored in batteries for later use, ensuring that no surplus energy is fed back into the grid. This is often a regulatory requirement or a deliberate strategy to minimize grid disturbances or maximize self-consumption of renewable energy.
In addition to dynamic active power limitation, grid operators in some markets may require system operators to equip their systems with a backup disconnection device (e.g. contactor or circuit breaker). This serves to provide galvanic isolation of the PV system if a defined switching threshold is exceeded. If your installation uses a backup disconnection device, the Automatic grid disconnection blue’Log XC license is required.
For more information, see the Zero feed-in whitepaper.
Set up zero feed-in
Prerequisites
A compatible meter. See Compatibility checker
The meter is installed at the grid connection point and delivers values for exported/imported power
blue'Log driver software is compatible with the inverters. See Compatibility checker
Firmware is 2.x.x or higher. If your version is below 2.x.x, contact technics@meteocontrol.com
Steps
Set up the meter
Set up the meter under Devices > Meter. Ensure that the sign of the imported power (from the grid) is negative. The sign can be changed using the Reference arrow system under the meter setup.
Check the sign of the imported power under Cockpit > Charts > Chart.
Under Devices > Meter, Define the device role as Feed in and import.
Configure power control
Configure the general data under Power control > Plant data.
Select the feed-in-meter.
Configure active power limitation
Enable the operation mode Closed loop.
Select the setpoint command method Pvarfix and define the power setpoint (e.g. 0% for zero feed-in).
Enable the Dynamic anti-windup toggle under Active power > Basic settings > Extended settings icon > System behavior.
Check that power control is working properly via the Power control tab (overview page).
Set up automatic grid disconnection
Prerequisites
A compatible meter. See Compatibility checker
The meter is installed at the grid connection point and delivers values for exported/imported power
blue'Log driver software is compatible with the inverters. See Compatibility checker
Firmware is 2.x.x or higher. If your version is below 2.x.x, contact technics@meteocontrol.com
Automatic grid disconnection license blue’Log XC
Steps
Set up the meter (see instructions above)
Configure power control (see instructions above).
Under Basic settings, select the setpoint command method Pvarfix.
Select the cog icon and define the power setpoint, for example 0% for zero feed-in.
Go to Basic settings > Extended settings icon > Options > Activate the automatic grid connection goggle.
Select the Output (command) and Logic level.
If you wish for grid disconnection to be dependent on power levels:
Activate the Grid disconnection dependent on power levels toggle.
Set the switching threshold for triggering the disconnection device.
Set a delay after which the disconnection should take place (recommended).
Check that power control is working properly via the Power control tab (overview page).
As an additional step, you can also configure an automatic grid connection for every failure state: setpoint failure, inverter failure (if activated), and meter failure. This can be used, for example, if you are not allowed to feed any electricity into the grid. Once you have activated the Automatic grid disconnection toggle as described above, go to Fail-safe operation, and activate the Automatic grid disconnection toggle.