Set up a KOSTAL Piko inverter
General tips
-
Have the data source (data logger, etc.) serial number on hand. When entering the serial number, pay attention to uppercase and lowercase letters and empty spaces.
-
The data source name can be freely selected. For recommendations, see our Naming guideline.
-
If possible, use data sources that support the same Measuring interval or align the intervals. Otherwise minor features may not work properly.
-
We strongly recommend ticking the check box Automatic device creation to ensure that VCOM automatically creates any new devices found during each data import.
-
If possible, perform a connection test once you have completed the configuration in both VCOM and the data source.
Data loggers only
-
For data loggers, update the firmware to the latest version prior to configuration.
-
For data loggers, any import that uses FTP can also use SFTP. The access data, such as the FTP server address, user name, and password remain identical. Only the port changes from port 21 (FTP) to port 2222 (SFTP).
APIs only
-
If you experience import issues with the API, please contact the respective API provider first.
-
Each day at midnight, VCOM checks for complete data and requests data from the past 7 days. If there are no limitations from the API and the data is available, the gaps will be filled.
Configuration details
|
Protocol |
HTTP |
|---|---|
|
File format |
DAT |
|
Measuring interval |
5 min |
|
Server |
|
|
Port |
80 |
Configuration: Inverter
-
Connect to the web interface of the Kostal Piko inverter. If you do not know the IP address, call up the web interface using the serial number (http: // [SERIALNUMBER])
-
Enter your login information. Factory setting:
Username: pvserver
Password: pvwr -
Enter the identifier P202L in the Portal Code field. Select Apply.
-
Enter the words go online in the Portal Code field. Select Apply.
-
A test transmission will start. If your inverter has already measured yield data, these will be transferred to the VCOM portal within the next five minutes.
-
Switch back to the inverter start page (Info) and close the Internet browser.
-
The setup of your inverter is now complete.
Configuration: VCOM
Prerequisites
-
User group technical customer or higher
-
At system level , go to
System settings >
Data sources > Data logger overview.
-
Under New source of type, select Kostal as the data source type from the dropdown.
-
Select Add.
-
Fill in required input fields.
-
Select Register new data logger.
Note
The inverter normally only sends data to the VCOM portal once per day (approx. 11:00 p.m.).