Controller freeze
Last modified:
About controller freeze
During overvoltage or undervoltage events, inverters enter Fault Ride Through (FRT) mode and ignore external control commands. This can cause the controller's correction values to increase. Once the event ends and inverters resume following commands, this mismatch can cause power oscillations. The Controller freeze function prevents such issues by “freezing” correction values (holding them constant) during the event. This ensures a smoother transition back to normal operation and enhances overall grid stability.
When activated, controller freeze works in 3 phases:
Event detection: The controller automatically detects an overvoltage or undervoltage event
Behaviour during event: The controller freezes the last correction values for active and reactive power
Return to normal operation: Once the freezing time has expired, the controller resumes calculating new correction values
Configure controller freeze
Steps
Navigate to Power Control > Reactive power >
Extended settings
In the Behaviour in event of error tab, activate the Controller freeze toggle.
Set the parameters as per the table below. The default values are already pre-configured.
The function is active. Controller freeze will be triggered the next time the voltage thresholds are “violated”/reached.
Parameter | Description |
---|---|
Voltage threshold undervoltage | Should match the voltage level at which the inverters enter FRT mode. |
Voltage threshold overvoltage | Should match the voltage level at which the inverters enter FRT mode. |
Voltage criterion | Select how the event is detected:
|
Freezing time | Ideally, the freezing time should match how long the inverters ignore the controller values. |